AIR HANDLING
CUBICLE COOLER
(FOR NUCLEAR POWER PLANT)
Complete your industry air conditioning system with the reliable HI AIR KOREA(HAK) Cubicle Cooler(CC)!
HAK has developed different types of customizable CC in response to the highly demanding room air requirements for use in Nuclear Power Plants.
HAK CC is composed of filter, fan, cooling coil in compact casing.
Together with the other HAK air conditioning equipment, these CCs are your partners for bringing quality air into your environments.
- FEATURES
CASING
- Double skinned panels made of 0.8 mm thickness galvanized steel internal wall and 3.2~4.5 mm thickness SS400 external wall with 25 mm thickness glass wool insulation
- Each section shall have enough strength to meet the specified design loading including seismic acceleration, and access panels are provided where required for assembly or maintenance
- Casing design pressure is at least 1.25 times of fan shut off pressure per the requirements of ASME N509
BASE FRAME
- The base frame is made of carbon steel
- Rigid enough to support all components during shipping, lifting and operation
- Spaces between the frame are also considered for installation of drain pipe
FAN
- Centrifugal type
- Centrifugal type fan designed, constructed and tested in accordance with ASME AG-1
- Material of casing and impeller is SS400
- The centrifugal fan shall be of double width double inlet(DWDI) and non-over loading type
- V-belt driven, complete with fan belt guard
- The blade of the centrifugal fan shall be backward-inclined airfoil or backward-curved type
MOTOR
- Premium efficiency
- Cast iron casing
- IP 54/55 protection
- Power supply : 480Vac, 60Hz, 3-phase
- Service factor : 1.15(for TEFC), 1.0(for TEAO)
- Enclosure : TEFC type(IC 411)
- NEMA design letter : B
COOLING COIL
- Chilled water coils are designed, constructed and tested in accordance with ASME AG-1
- Copper tube with aluminum fins
- Cooling medium : Chilled water
- AHRI certified
FILTER
- Frames are designed to withstand the operating pressure
- Filters are UL 900 classified
- CAPACITIES
MODEL NO. SUPPLY FAN
AIR FLOW RATEEXTERNAL
STATIC
PRESSURECOOLING CAPACITY DIMENSION WEIGHT m3/min Pa kcal/hr kW USRT W
(mm)H
(mm)L
(mm)kg HN-SCC-0040 40 400 3,030 3.5 1 1,520 1,980 970 750 HN-SCC-0070 70 450 6,050 7.0 2 2,100 2,100 970 760 HN-SCC-0100 100 400 9,080 10.5 3 2,100 2,100 970 790 HN-SCC-0140 140 600 12,100 14.0 4 2,200 2,100 970 800 HN-SCC-0200 200 600 15,130 17.5 5 2,300 2,200 970 900 HN-SCC-0300 300 700 30,300 35.0 10 2,300 2,300 1,100 1,200 HN-SCC-0520 520 800 45,450 52.5 15 2,300 2,300 2,000 2,000 HN-SCC-0850 850 1,320 90,900 105.0 30 2,300 2,300 2,500 2,400