메인콘텐츠 바로가기

HI AIR KOREA Co., Ltd.

KOREAN

HOME

INDUSTRY

DAMPER

SMOKE DAMPER
(FOR NUCLEAR POWER PLANT)

HI AIR KOREA SMOKE DAMPERS for nuclear power plant can be installed at HVAC systems provided for various buildings of a nuclear power plant.

HAK SMOKE DAMPERS are used to prevent the spread of smoke from the space of fire origin to other spaces in the same building. 

These dampers are available as safety related (SR) and non-safety related (NSR) items. Safety related dampers are fabricated with Q class components & dedicated commercial grade items, and verified for seismic qualification (SQ).

If necessary, they can be verified for environmental qualification (EQ).

  • FEATURES

    SMOKE DAMPER

    • Design base
      1. 1. DA of ASME AG-1 (KEPIC MH)
      2. 2. IEEE 323
      3. 3. IEEE 382 (KEPIC END 3700)
      4. 4. UL 555S
      5. 5. AMCA 500-D
    • Close automatically utilizing electro thermal link (ETL)
    • Power supply to electro thermal link
      (ETL shall be 120VAC or 24VDC)
    • Leakage classification Ⅰ in accordance with UL 555S
    Classification  Leakage, ft3/min/ft2 (=m3/s/m2 x 196)
    At 1.0 inch water (0.249 kPa)  At 4.0 inch water (0.995 kPa) 
    4 8
    II  10 20
    III  40 80
    IV  60 120
    Classification  Leakage, ft3/min/ft2 (=m3/s/m2 x 196)
    At 8.0 inch water (1.99 kPa)  At 12.0 inch water (2.99 kPa) 
    11 14
    II  28 35
    III  112 140
    IV  168 210

    STANDARD CONSTRUCTION FOR SMOKE DAMPER

    Part  Material 
    Frame  Carbon steel + Hot dip gal'v 
    Blade(Seat)  Carbon steel + Hot dip gal'v 
    Fusible link  ETL (Electro thermal link) 
    Blade seal  Silicon foam gasket 
    Shaft  Carbon steel + Electro galvanizing 

SALES MANAGER